Permissible continuous current for wires with copper conductors with rubber insulation in metal protective sheaths and cables with copper conductors with rubber insulation in lead, PVC, nitrite or rubber sheath, armored and unarmoured.
|
|
Conductor cross-section, mm 2 |
Current *, A, for wires and cables |
single-core |
two-core |
three-core |
when laying |
in the air |
in the air |
in the ground |
in the air |
in the ground |
1.5 |
23 |
19 |
33 |
19 |
27 |
2.5 |
thirty |
27 |
44 |
25 |
38 |
4 |
41 |
38 |
55 |
35 |
49 |
6 |
50 |
50 |
70 |
42 |
60 |
ten |
80 |
70 |
105 |
55 |
90 |
16 |
100 |
90 |
135 |
75 |
115 |
25 |
140 |
115 |
175 |
95 |
150 |
25 |
170 |
140 |
210 |
120 |
180 |
50 |
215 |
175 |
265 |
145 |
225 |
70 |
270 |
215 |
320 |
180 |
275 |
95 |
325 |
260 |
385 |
220 |
330 |
120 |
385 |
300 |
445 |
260 |
385 |
150 |
440 |
350 |
505 |
305 |
435 |
185 |
510 |
405 |
570 |
350 |
500 |
240 |
605 |
- |
- |
- |
- |
|
|
* Currents refer to wires and cables with and without a zero core. |
|
Permissible continuous current for cables with aluminum conductors with rubber or plastic insulation in lead, PVC and rubber sheaths, armored and unarmoured.
|
|
Conductor cross-section, mm 2 |
Current *, A, for wires and cables |
single-core |
two-core |
three-core |
when laying |
in the air |
in the air |
in the ground |
in the air |
in the ground |
2.5 |
23 |
21 |
34 |
19 |
29 |
4 |
31 |
29 |
42 |
27 |
38 |
6 |
38 |
38 |
55 |
32 |
46 |
ten |
60 |
55 |
80 |
42 |
70 |
16 |
75 |
70 |
105 |
60 |
90 |
25 |
105 |
90 |
135 |
75 |
115 |
35 |
130 |
105 |
160 |
90 |
140 |
50 |
165 |
135 |
205 |
110 |
175 |
70 |
210 |
165 |
245 |
140 |
210 |
95 |
250 |
200 |
295 |
170 |
255 |
120 |
295 |
230 |
340 |
200 |
295 |
150 |
340 |
270 |
390 |
235 |
335 |
185 |
390 |
310 |
440 |
270 |
385 |
240 |
465 |
- |
- |
- |
- |
|
|
Note: Permissible continuous currents for four-core cables with plastic insulation for voltages up to 1 kV can be selected according to the table, as for three-core cables, but with a factor of 0.92.
|
|
Copper conductors |
Machine current, A |
Cable section mm 2 |
Machine current, A |
Aluminum conductors |
power, kWt |
Current, A |
power, kWt |
Current, A |
220 V |
380 V |
220 V |
380 V |
3.3 |
6.4 |
15 |
ten |
1.5 |
|
|
|
|
4.6 |
nine |
21 |
twenty |
2.5 |
16 |
3.5 |
6.8 |
16 |
5.9 |
11.5 |
27 |
25 |
4 |
twenty |
4.6 |
nine |
21 |
7.4 |
14.5 |
34 |
32 |
6 |
25 |
5.7 |
11.1 |
26 |
eleven |
21.4 |
50 |
50 |
ten |
32 |
8.3 |
16.3 |
38 |
15.4 |
thirty |
70 |
63 |
16 |
50 |
12.1 |
23.5 |
55 |
18.7 |
36.4 |
85 |
80 |
25 |
63 |
14.3 |
27.8 |
65 |
22 |
42.9 |
100 |
100 |
35 |
63 |
16.5 |
32.1 |
75 |
|