Professional cable systems

Specifications BL BH

Diameter of corrugated pipes:
16-50 mm
Material of corrugated pipes:
HDPE composition
Standard:
GOST R IEC 61386.1-2014
Degree of protection of corrugated pipes:
IP 55 according to GOST 14254 (IEC 529)
Installation conditions for corrugated pipes:
for hidden wiring in wall grooves, in a screed floors made of concrete and / or non-combustible materials, in monolithic concrete construction Installation
temperature for corrugated pipes:
from -40 ° C to + 90 ° C
Minimum bending radius:
3 diameters
Strength of corrugated pipes:
Over 350N by 5 cm at 20 ° C (light series) , over 750N per 5cm at 20 ° С (heavy series)
Dielectric strength of corrugated pipes:
not less than 2000 V (50 Hz, for 15 minutes)
Insulation resistance of corrugated pipes:
not less than 100 MOhm (500 V, for 1 min)

Accessories

  • Box dimensions (AxVxH): 80x80x36 - 310x240x125 mm
  • Protection degree: IР44 - IР55
  • Number of sealed entries: 4-10
  • Application: for outdoor wiring / indoor wiring,

Corrugated pipe selection table depending on the number of wires and cross-sectional dimensions

Cross
- sectional area of ​​the wire, mm2
Number of wires, pcs. Pipe outer diameter, mm
1.5 2/3/4/5 16/16/20/20
2.5 2/3/4/5 16/16/20/25
4 2/3/4/5 20/20/25/25
6 2/3/4/5 20/25/32/32
ten 2/3/4/5 25/32/32/40
16 2/3/4/5 32/32/40/40
25 2/3/4/5 32/40/50/50
35 2/3/4/5 40/50/50/63
50 2/3/4/5 50/50/63/63
70 2/3/4 50/63/63
95 2/3 63/63
120 2 63
150 2 63